30
30
20
20
10
10
0
01020
1.0 FC
0.1 FC
0.5 0.3 0.2
30 40
Distance from source (in feet)
Distance left
(in feet)
Distance right
(in feet)
50 60 70
LED Status Condition Meaning of the Indication
No light AC power is removed from the circuit
• Steady light (no blinking) Fully charged
• Light blinks once Charging
• • Light blinks twice Battery failure
• • • Light blinks three times Circuit failure
• • • • Light blinks four times Lamp failure
33.00 EXS/EXD
35.63 EXD GB
30.00 EXS/EXD
30.63 EXD GB
6.50
1.13 EXS/EXD
2.13 EXD GB
7.00 EXS/EXD
8.38 EXD GB
11.00
11.13
12.81
16.50
29.63
14.75
S UGGESTED SPECIFICATION
General
The emergency lighting system shall be explosionproof
and dust-ignitionproof, UL Listed (UL844) for Class I,
Groups B, C, D; Class II, Groups E, F, G; and Class III.
Power supply also shall be UL Listed as “Emergency
Lighting and Power Equipment” (UL924). System shall
be rated 120, 220, 240, 277 VAC; with a 12 VDC
output supply to the lamps. Unit shall be furnished
with a push-to-test switch and AC monitor pilot light
as standard; and optional integral battery disconnect
switch. All fi eld connections to be made to a terminal
block, also provided as standard. The emergency light
system shall perform an automatic 30-second test and
self diagnostic at least once every 30 days and provide
visual indication of a potential fault.
Lighting Fixtures
Lighting fi xtures shall be factory sealed and made of
copper-free aluminum with corrosion resistant epoxy
fi nish and gasketing as standard. Between the EVLA12
lamp heads and the ELPS50 power supply there is a
factory installed seal. Conduit entry must be sealed
within 18" of the power supply in accordance with
the NEC. Fixtures shall be as furnished with 14 watt
tungsten halogen lamps with faceted inner refl ectors
for beam direction, and shall be adjustable on two axes
and capable of being locked in place. Fixtures shall be
capable of being remote mounted. Fixtures shall be
UL Listed (UL844) for Class I, Groups B, C, D; Class
II, Groups E, F, G; and Class III applications. Fixtures
shall also be UL Listed for 55ºC elevated ambient
temperature for remote mounting applications.
P HOTOMETRICS
D IMENSIONS (INCHES)
Mexico • Latin America/Caribbean • Germany • Australia • Asia • Dubai • India
Solutions.Worldwide.
TM
Crouse-Hinds is a registered trademark of Cooper Industries, Inc.
4867-1005 © 2005 Cooper Industries, Inc. Printed in U.S.A
In the U.S.:
Cooper Crouse-Hinds
P.O. Box 4999
Syracuse, NY 13221
(315) 477-5531
FAX: (315) 477-5179
In Canada:
Cooper Crouse-Hinds Canada
(905) 507-4187
FAX: (905) 568-7048
For more information: Contact an authorized Cooper Crouse-Hinds Distributor, Sales Office or Customer Service Department:
Distributed by:
For office locations outside of North America or for additional product
information, visit our website at: www.crouse-hinds.com
ELPS LIGHT-PAK
TM
Emergency Lighting System For Hazardous Areas
S TATUS INDICATION